ncw-fuellstand.png: Capacitive  Level Limit Switch NCW

Capacitive Level Limit Switch NCW

For liquids

Electrodes: max. 4 m
Contact: 1 relay (max. 250 VAC, 1A)
Connection:
G 1 male thread, stainless steel or G 2 male thread, PVDF
Material electrodes:
stainless steel with PTFE or PVDF coating
pmax: 30 bar
tmax: 90°C (125°C)
Power supply: 24, 110, 230 VAC, 18 ... 36 VDC

Datasheet

application/pdf; charset=binary

n1gb_ncw

211 KB

Description

The KOBOLD capacitive level indicators type NCW serve to monitor liquid levels in tanks. They consist of a measuring probe and a connecting head with a plug-in evaluation module. Depending on the operating conditions, different probes are available:

- single probe for standard applications

- double probe with PVDF connection for non
metallic tanks and at the same time aggressive medias

- single probe with external reference tube for non metallic
tanks or media with very low dielectric constant and

- single probe with a split connecting head for liquid
temperatures of up to 125 °C.

The devices do not have any mechanically moving parts and therefore hardly any mechanical wear. The plug-in evaluation modules can be changed easily so that the de vices are really easy to maintain.