KOBOLD Instruments Inc • 1801 Parkway View Drive • 15205 Pittsburgh, PA • Tel: +1 412 788 2830 • E-mail: Please activate JavaScript visit koboldusa.com

att-k-analyse.png: Transmitter for Turbidity Measurement System ATT-K

Transmitter for Turbidity Measurement System ATT-K

COMPACT-LINE

0 ... 200 mS/cm
With panel mount housing or field mounting housing
Display of conductivity and temperature with LEDs
analogue actual-value output scaleable
2 relays for control functions (PID) programmable
2 binary inputs
1 binary output (alarm contact or temperature limit contact)

Datasheet

application/pdf; charset=binary

ats-k-gb-analysis

319 KB
application/pdf; charset=binary

a1gb_acm-z

177 KB

Description

The transmitted light and scattered light signals generated in the sensor are amplified in the KOBOLD transmitter ATT-K to produce a weighted ratio. The measured variable thus created is proportional to the total volume of particles in the carrier medium. Two independently adjustable switch points as well as a mA output are available for alarm signalling, or control and regulating.

An additional relay output (FAIL-SAFE) signals lamp or system failures. Basic system calibration is carried out as standard in ppm DE (mg infusorial earth / L water). The device may also be calibrated to FTU (Formazin Turbidity Standard) or to EBC (European Brewery Convention) if required.

Other Members of the KOBOLD group