auf-zubehoer.png: Plug-On Display for Transmitters AUF

Plug-On Display for Transmitters AUF

Universal mounting on transducers with 4 - 20 mA output und plug EN 175301-803 form A

4 - 20 mA loop powered
Indicator: 4-digit, red LED
Indicating range: -1999 ... +9999
Accuracy class: 0.2 % of span ±1 digit
Option: open collector, Ex-version

Datasheet

application/pdf; charset=binary

auf-gb-accessories

295 KB

Operating Instructions

application/pdf; charset=binary

AUF - Operating Instructions

229 KB
application/pdf; charset=binary

AUF-2000 - Operating Instructions

872 KB

Miscellaneous

application/pdf; charset=binary

General Safety Instructions

190 KB

Approvals

application/pdf; charset=binary

BVS 17 ATEX E 022

II 2G Ex ib IIC T4 Gb

2,4 MB
application/pdf; charset=binary

IECEx BVS 17.0012

Ex ib IIC T4 Gb

4,1 MB

Description

The model AUF-... plug-on display is a universal local display suitable for use with various transmitters. The transmitter must be fitted with an analogue output and a connector in accordance with DIN 43 650. Model AUF-2000 can be delivered for use in hazardous areas. The plug-on display is simply plugged in between connector and socket; it is then ready for operation.
The plug-on display is user programmable. Scaling, the position of the decimal point, gate time and switch point (optional) may be set with two keys. The menu steps are output to the LED display field. The plug-on display is supplied by the current loop of the 4 - 20 mA signal transmitter. No additional auxiliary power is required. The programmed parameters are stored in an EEPROM; they are therefore not lost after power failure.
Over or under range are displayed as a message on the LED display. All device functions are continuously monitored by an integral diagnostic system. The indicating unit can be rotated in 90° steps; it can thus be adapted to different installation positions. The integral open-collector output, available as an option, allows a transmitter to be retrofitted easily with a limit contact.

Other Members of the KOBOLD group

Products by Keyword
KOBOLD Instruments Inc.

1801 Parkway View Drive
15205 Pittsburgh PA
United States of America

Please activate JavaScript

Cookies & Features

This website uses cookies to provide content and features. Details of the technologies used can be found in our privacy policy.

Essential Cookies

Session data such as language selection or spam protection - you can't do without it.

Google Media

Some pages on this website load content from Google Maps and YouTube.

loading
loading